Tests
Processes
Tests

We test façade elements and construction materials, including product classification, professional engineering and validity evaluation services. We test and evaluate structural physics and design criteria befitting international standards. These criteria are then compared to the relevant standards (Air, Water, Wind, Sound, Heat, Seismic, Impact, and Corrosion). We also test performance requirements of new or existing projects and compare the performances of façade and structural elements.

Air Permeability Test

In Air Permeability Tests, the air infiltration of curtain walls and doors / windows is measured for both fixed and open able elements according to EN 12153 and EN 1026. During the tests, the sample is subjected to both positive and negative pressures reaching up to 10 000 Pa in façade samples and 5000 Pa in window / door samples. Air penetration intensity is expressed as m³ / hour. The results of the tests are defined as air permeability per unit area and air permeability per unit length of sealing as m³ / h.m² and m³ / h.m respectively.

Water Penetration Test

In Water Penetration Tests, water penetration in curtain walls and doors / windows is measured for both fixed and open able elements in compliance to EN 12155 and EN 102. During the tests, the sample is subjected to positive test pressure applied at fixed intervals and with increased pressure, so that a certain amount of water is applied to the surface to form a continuous layer.

Wind ResistanceTest

In Wind Load Tests, resistance of curtain walls and doors / windows against wind load is determined under positive and negative wind pressures for both fixed and openable elements according to EN 12179 and EN 1221. During this test, a series of positive and negative test pressures reaching 10 000 Pa in specified intervals are applied to the test sample. For each test pressure, measurements are made to evaluate resistance to damage from wind loads and to assess perpendicular deflection on the surface. The deflection should be less than L / 200 or 15 mm.

Water Penetration Test of Façade and Window / Door Systems Under
Dynamic Pressure / AAMA 501-1

In this test an airplane engine gene rates wind velocities up to 45 m / sec, which throws spray water coming from a specially designed system onto the sample. As the result, the locations of water penetration (if any) are recorded and added to the report.

ENV 13050 Laboratory Test Under Dynamic Air Pressure and Water Spray
Dynamic Pressure / AAMA 501-1

In European norm instead of an airplane engine propeller, electrical motor driven fun is used. Special spraying nozzles are capable of spraying 2 to 500 litres of water per minute, and this water is then thrown on to the test sample via wind from a special fan pipe couple at speeds of 108 km / h. The mockup is observed from the inside during the test to discover if the water penetrates, and the exact locations where it does.

Impact Resistance Tests EN 12600, EN 14019, EN 13049
Dynamic Pressure / AAMA 501-1

These tests can be classified as “hard body” and “soft body” tests and can be applied on façade, window / door, skylight and balustrade systems. Respectively for each test, either a mass of 50 kg. consisting of two rubber wheels around a steel bore, or a sack full of glass marbles weighing 50 kg. is swung to the test sample via standard pendulum movement.

The applied energy is the potential energy gained by letting go of the bag and allowing it to impact on the glass. This is expressed in Joule ( J ) units. Up to 1200 J can be applied on the sample as part of this process. The impact test can be performed on the inner or the outer surface of the test sample, for the test to be successful, there should be no permanent deformation nor any residual debris on any part of the test sample.

Impact Resistance Tests EN 12600, EN 14019, EN 13049

These tests can be classified as “hard body” and “soft body” tests and can be applied on façade, window / door, skylight and balustrade systems. Respectively for each test, either a mass of 50 kg. consisting of two rubber wheels around a steel bore, or a sack full of glass marbles weighing 50 kg. is swung to the test sample via standard pendulum movement.

The applied energy is the potential energy gained by letting go of the bag and allowing it to impact on the glass. This is expressed in Joule ( J ) units. Up to 1200 J can be applied on the sample as part of this process. The impact test can be performed on the inner or the outer surface of the test sample, for the test to be successful, there should be no permanent deformation nor any residual debris on any part of the test sample.

Building Movement Tests AAMA 501.4 (Static) / AAMA 501.6 (Dynamic)

The seismic behaviors of façade systems are tested with three dimensional pneumatically seismic test units in accordance to AAMA 501.4 and AAMA 501.6. Horizontal displacements between two floors up to 150 mm and in dynamic tests, frequencies of 0.4 and 0.8 Hertz can be applied onto the samples. As a result, any risks of falling glass and permanent deformations are looked for, and if found, recorded to the report.

ISO 10140 - 2 Airborne Sound Insulation of Building Elements

This test consists of two adjacent rooms with an opening in between for the sample to be installed. In one of the rooms (source room) noise is produced and noise level in the other room is measured. After the sample is checked thoroughly for leakage, the noise level of the rooms with the source and receiver are measured and the difference is found.

All measurements are done at the third octave and 50-5000 Hz frequencies according to ISO 10140-2, and as a result, a final value describing the general acoustical performance is found.

ISO 10848 - 2 Sound Insulation Measurements - Flanking Transmission

The facility consists of four adjacent rooms which allow the horizontal, vertical, and diagonal sound transmission to be measured.

Component Cycling Test EN 947, EN 948, EN 12046 - 2, EN 1191

This test serves to observe fatigue mechanical resistance and permanent deformation of window / door systems after a specific amount of opening and closing cycles.

Mechanical Durability of Silicon Elements Tests

The guarantee of endurance for Structural Silicon Façade Systems against aging is provided by tests which are carried out in climatic aging and ultraviolet light application cabins. To check if the silicon bonding process has been applied properly between the glass and aluminum profile, samples are taken at fixed intervals during the production process and are tested according to international norm ETAG 002. The production process is checked daily, using tensile testing and rupture test equipment. Furthermore, our silicon application process has been approved by the French CSTB organization. European Technical Approvals Publications ETAG 002 and CSTB 3488.

EN 13051, AAMA 501.2 - 03 Water Penetrations of Façade Systems
According to the EN 13051 norm, with this on site test, a fixed volume of constantly flowing water is sprayed onto the outer surface of the newly installed curtain wall, and a continuous water flow is maintained.

EN 13829 Air Permeability and Thermal Performance Test under Dynamic Pressure
This test measures the air permeability of the whole or some part of a building according to the EN 13829 standard. 50 Pascals of pressure difference is applied on the system to be tested with a special fan, and if the resulting air exchange value exceeds 3 m³ / hr, the test is considered a failure.

ISO 140 - 5 On - Site Testing of Airborne Sound Insulation Value
With this test, the real on site sound reduction value of a façade element is measured. Sources distanced 5 metres from the façade create a stable field of sound between 50 and 5000 Hz, and after the receptors measure the echoes, a final average sound absorption value is calculated.